Four everyday calculations: hood airflow, duct diameter, filter area, and temperature and pressure correction. Enter what you know and get an instant result for preliminary selection.

Request a Technical Assessment
01

Before you start

Establish the process, measuring points and actual temperature and pressure before choosing a tool. Blank fields are not calculated; you can load example values to try it; recalculate after changing inputs.

02

Hood airflow: Q = 3600·A·v

A is the effective hood area (m²), v the average face velocity (m/s) and Q the airflow (m³/h). The further an external hood is from the source, the higher the velocity it needs; allow for rising hot plumes and cross-drafts.

03

Duct diameter: D = √(4Q / 3600πv)

With Q in m³/h and duct velocity v in m/s, D comes out in metres. After choosing a standard size, recheck velocity and resistance, allowing for conveying, wear and noise; recalculate when branches close or stations are added.

04

Filter area: A = Q / (60·V)

With Q in m³/h and filtration velocity V in m/min, A comes out in m². This applies to dry cartridges and bags; use a lower velocity for moist, sticky or heavy dust.

05

Temperature and pressure: Q₂ = Q₁·(T₂/T₁)·(p₁/p₂)

Use kelvin (°C + 273.15) and absolute pressure (kPa). This suits ordinary gas streams; with condensation, reactions or added air, work out the gas quantity first.

06

Saving your results

The copied record includes the formula, units, inputs and result. Send it to us with your layout and equipment details and we can recommend a configuration faster.