Filtration Velocity and Filter Area

Filter area = airflow ÷ (60 × filtration velocity). A lower velocity eases the load on the media and extends its life but needs a larger collector. Choose the velocity for the dust and media, then calculate the area.

Request a Technical Assessment
Three active filter chambers above two active chambers and an isolated third chamber below.
The two rows compare two operating states of the same equipment. Open full diagram ↗

A worked example

At 7,200 m³/h actual inlet airflow and 0.80 m/min, A = 7,200 ÷ (60 × 0.80) = 150 m². At 1.00 m/min, A = 7,200 ÷ 60 = 120 m².

Area falls during maintenance

If the 150 m² comes from three 50 m² compartments and one is taken offline, only 100 m² remains and filtration velocity becomes 7,200 ÷ (60 × 100) = 1.20 m/min. Check that this state is acceptable when selecting.

Choosing filtration velocity

  • Fine fume from welding and laser cutting: use the lower end. SCALES lists SCU airflow for 0.85–1.2 m/min.
  • Heavy, sticky or damp dust: lower values, or use a baghouse or wet collector.
  • Use the actual airflow at the collector inlet; correct hot gas to its actual temperature.