TECHNICAL KNOWLEDGE
What Causes Pressure Loss in an Extraction System?
System resistance is the sum of pressure losses across hoods, ducts, elbows, dampers, the collector and the outlet. The fan must overcome the resistance of the worst path, or the design airflow will not be reached.
Request a Technical Assessment
A worked example
Design airflow 7,200 m³/h; along the farthest path: hood 180 Pa, branch 420 Pa, main duct and fittings 260 Pa, collector 900 Pa, outlet 140 Pa, totalling 1,900 Pa.
The power delivered to the air = airflow (m³/s) × pressure (Pa) = 2.00 × 1,900 = 3,800 W, or 3.8 kW. Fan, drive and motor losses mean the motor must be larger.
Where resistance comes from
- The collector: resistance rises as media loads, so size the fan for the running condition, not new filters.
- Elbows and tees: tight bends and right-angle tees add a lot.
- Small or long ducts: resistance rises with the square of velocity.
- Unbalanced branches: near branches take the air and far ones starve; balance with dampers.
Reducing resistance
Place the collector close to the sources to shorten the main duct; use long-radius elbows; clean on pressure drop to keep media resistance in range; add a VFD to match airflow to demand.
