Estimating Airflow: How to Use Q = A × v

Airflow equals opening area times average velocity through it: Q = 3600 × A × v (Q in m³/h, A in m², v in m/s). It is the most common way to estimate airflow for hoods, openings and ducts.

Request a Technical Assessment
Nine measurement positions across a rectangular duct section, with forward airflow and an enlarged measurement connection.
The grid represents velocity measurements across one section. Open full diagram ↗

Formula and units

  • A: effective opening area; for a rectangle, A = width × height.
  • v: average velocity through the opening, in m/s.
  • 3600 converts per second to per hour.

A worked example

A booth opening 0.60 m wide and 0.40 m high has A = 0.60 × 0.40 = 0.24 m². At 0.50 m/s, Q = 3600 × 0.24 × 0.50 = 432 m³/h.

What it does not tell you

The formula gives the airflow through the opening; it does not guarantee that fume outside is drawn in. Suction falls off quickly with distance: doubling the distance roughly quadruples the airflow needed. Draughts, obstruction by the part and rising heat also matter. So place the hood close and enclose first, then calculate, and confirm in real work after installation.